IO-8TCS-E
These Remote I/O Modules are designed for Ethernet Modbus TCP communication, ideal for data acquisition and control systems.
- High Reliability: Ensures dependable performance in industrial environments.
- Ease of Installation and Maintenance: Simplifies setup and reduces downtime for maintenance.
- Cost-Effective Solution: Ideal for industrial measurement and monitoring applications.
- Seamless Integration: Can be easily added to existing Ethernet Modbus networks.
- Versatile Selection: Various types of I/O Modules are available to meet user-specific requirements.
- LED Indicators: Provides clear status monitoring for digital inputs/outputs and fault diagnostics.
- Interchannel Isolation: Special modules offer isolation between channels for added safety and performance.
- Modbus TCP Protocol: Modules feature an Ethernet interface supporting the Modbus TCP protocol.
Features
- Modbus TCP Modules for Data Acquisition and Control Systems
- Extremely cost-effective modules for industrial measurement and monitoring applications
- A wide range of modules for various digital and analog inputs and outputs
- Wide range of baud rates available in Modbus RTU modules
- Built-in web server in Modbus TCP modules for Monitoring real-time data and configuration
- Isolated modules available for special application
- User-friendly Setup software for Configuration and Troubleshooting
- Optional Data acquisition software for data acquisition and analysis on PC
- Interface with field devices to provide real-time data for SCADA/PLC/HMI
- Integration with the 3rd party software via Modbus TCP Protocol
- Front panel status LEDs on every module for digital IO status, communication, and power supply
Parameters | Modbus TCP IO Modules | ||
Interface | Ethernet Modbus TCP | ||
Communication Speed | 10/ 100 MBPS | ||
Operating Temperature | -10℃ to 50℃ | ||
Storage Temperature | -40℃ to 85℃ | ||
Humidity | Up to 95% Non-condensing | ||
Mounting | DIN Rail | ||
Weight | 105 grams | ||
Dimensions( W*H*D) | 23*109*98 mm | ||
Approval Standard | Safety | IEC950 | |
Connectors | EMC | IEC 61000-4-2-A1 Level2, IEC 61000-4-3-A1 Level2, IEC 61000-4-4 Level3, CISPR 11:1997-A1, EN55011:1998 Group1 Class A | |
Input | 18 Way screw connector on front | ||
Communication | RJ45 on topside of the unit | ||
Logic Power | 4 Pin Connector on bottom side of unit |
Type of Input | Thermocouple. mV | |
No. of Channels | 8 | |
Power Supply | Logic Supply Voltage | 12 to 24 VDC |
Logic Supply Current | 105mA @ 12 V / 54mA @ 24V | |
Field Supply Voltage | N.A. | |
Field Supply Current | N.A. | |
Voltage Input Range | 0 to 50mV, ± 100mV | |
RTD Type | N.A. | |
Thermocouple Type | J, K, E, T, N, B, S, R, C, D, G | |
Cold Junction | CJC Error: ±0.5°C Typically After 30 Minutes warm up time. | |
Burnout Detection | Yes | |
Accuracy | 32 Bits | |
Frequency | ± 0.05% FSR | |
Resolution | 0.1°C | |
Sampling Rate | 37 Samples / Minute | |
Isolation between Channels | 350 V Peak | |
Isolation between Field and Logic | 1500 VRMS | |
Drift | 100 ppm/°C |